USER MANUAL – Release 1.2 of 01/01/2010
Page 167 of 191
Version: 02/03/2010
57.15
DOMESTIC HOT WATER PUMP FLOW SWITCH ALARM
Display label meaning
AHFL
(domestic hot water pump flow switch alarm)
Cause of activation
(the flow switch alarm is only active with FS01
!
0)
ID active for the AL16 time from water pump start-up, after ID active for AL18
time
Reset
ID not active for the time AL19
Reset
Automatic – it becomes manual if ID active for time AL17 counted from the
expiry of AL18 (reset procedure in functions menu)
Icon
flashing
Action
Alarm + buzzer relays only activated if the flow switch alarm is activated in
normal working phase
Regulators
Alarm
Relay + buzzer only activated if the flow switch alarm is activated in normal
working phase
Domestic hot water pump
Off when the alarm becomes with manual reset
Production of domestic hot
water function
Off
Other loads
They follow their regulation
57.16
DOMESTIC SOLAR PANELS WATER PUMP FLOW SWITCH ALARM
Display label meaning
APFL
(solar panels pump flow switch alarm)
Cause of activation
(the flow switch alarm is only active with FS01
!
0)
ID active for the AL16 time from water pump start-up, after ID active for AL18
time
Reset
ID not active for the time AL19
Reset
Automatic – it becomes manual if ID active for time AL17 counted from the
expiry of AL18 (reset procedure in functions menu)
Icon
flashing
Action
Alarm + buzzer relays only activated if the flow switch alarm is activated in
normal working phase
Regulators
Alarm
Relay + buzzer only activated if the flow switch alarm is activated in normal
working phase
Solar panels water pump
Off when the alarm becomes with manual reset
Solar coil on/off valve
Active
Other loads
They follow their regulation