NOTE!
A change in mode via the digital inputs can only take
place if
T-08 Timed Actions Mode
is set for
[0] Times Actions
Auto
.
If commands are applied simultaneously to the digital
inputs for Constant OFF and Constant ON, Timed Actions
mode will change to Timed Actions Auto and the two
commands will be disregarded.
If
0-70 Set Date and Time
is not set or the adjustable
frequency drive is set to HAND or OFF mode (e.g., via the
LCP), Timed Actions mode will be change to
Timed Actions
Disabled
.
The Timed Actions have a higher priority than the same
actions/commands activated by the digital inputs or the
Smart Logic Controller.
NOTE!
The clock (parameter group K-7#) must be correctly
programmed for Timed Actions to function correctly.
NOTE!
When mounting an Analog I/O OPCAIO option card, a
battery backup of the date and time is included.
23-00 ON Time
Array [10]
Range:
Function:
0 N/A
*
[0 - 0
N/A]
Sets the ON time for the timed action.
NOTE!
The adjustable frequency drive has no
backup of the clock function and the set
date/time will reset to default
(2000-01-01 00:00) after a power-down
unless the Analog I/O option module
(OPCAIO) with battery backup of the Real
Time Clock is installed. In
0-79 Clock Fault
,
it is possible to program for a warning in
case the clock has not been set properly,
e.g., after a power-down.
23-01 ON Action
Arra [10]
Option:
Function:
Select the action during ON Time.
See
13-52 SL Controller Action
for
descriptions of the options.
[0]
*
DISABLED
[1]
No action
[2]
Select set-up 1
[3]
Select set-up 2
23-01 ON Action
Arra [10]
Option:
Function:
[4]
Select set-up 3
[5]
Select set-up 4
[10] Select preset ref 0
[11] Select preset ref 1
[12] Select preset ref 2
[13] Select preset ref 3
[14] Select preset ref 4
[15] Select preset ref 5
[16] Select preset ref 6
[17] Select preset ref 7
[18] Select ramp 1
[19] Select ramp 2
[22] Run
[23] Run reverse
[24] Stop
[26] Dcstop
[27] Coast
[28] Freeze output
[29] Start timer 0
[30] Start timer 1
[31] Start timer 2
[32] Set digital out A low
[33] Set digital out B low
[34] Set digital out C low
[35] Set digital out D low
[36] Set digital out E low
[37] Set digital out F low
[38] Set digital out A high
[39] Set digital out B high
[40] Set digital out C high
[41] Set digital out D high
[42] Set digital out E high
[43] Set digital out F high
[60] Reset Counter A
[61] Reset Counter B
[70] Start Timer 3
[71] Start Timer 4
[72] Start Timer 5
[73] Start Timer 6
[74] Start Timer 7
How to program the adjustab...
VLT AQUA 12-Pulse High Power Instruction Manual
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark
6-31