6.1.2 Quick Menu Mode
The GLCP provides access to all parameters listed under
the Quick Menus. To set parameters using the [Quick
Menu] button:
Pressing [Quick Menu] the list indicates the different areas
contained in the quick menu.
Efficient parameter set-up for water applications
The parameters can easily be set up for the vast majority
of the water and wastewater applications only by using
the [Quick Menu].
The best way to set parameters using the [Quick Menu] is
by following the steps below:
1.
Press [Quick Setup] for selecting basic motor
settings, ramp times, etc.
2.
Press [Function Set-ups] for setting up the
required functionality of the adjustable frequency
drive - if not already covered by the settings in
[Quick Setup].
3.
Choose between
General Settings, Open-loop
Settings
and
Closed-loop Settings
.
It is recommended to do the set-up in the order listed.
Figure 6.1 Quick Menu view.
Par.
Designation
[Units]
0-01
Language
1-20
Motor Power
[kW]
1-22
Motor Voltage
[V]
1-23
Motor Frequency
[Hz]
1-24
Motor Current
[A]
1-25
Motor Nominal Speed
[RPM]
3-41
Ramp 1 Ramp-up Time
[s]
3-42
Ramp 1 Ramp-down Time
[s]
4-11
Motor Speed Low Limit
[RPM]
4-13
Motor Speed High Limit
[RPM]
1-29
Automatic Motor Adaptation (AMA)
Table 6.2 Quick Setup parameters. Please see section
Commonly Used Parameters - Explanations
If
No Operation
is selected in terminal 27, no connection to
+24 V on terminal 27 is necessary to enable start.
If
Coast Inverse
(factory default value) is selected in
Terminal 27, a connection to +24V is necessary to enable
start.
For detailed parameter descriptions, please see the
following section on
Commonly Used Parameters - Explan-
ations
.
6.1.3 Q1 My Personal Menu
Parameters defined by the user can be stored in Q1 My
Personal Menu.
Select
My Personal Menu
to display only the parameters,
which have been pre-selected and programmed as
personal parameters. For example, a pump or equipment
OEM may have pre-programmed these to be in My
Personal Menu during factory commissioning to make on-
site commissioning / fine tuning simpler. These parameters
are selected in par. 0-25
My Personal Menu
. Up to 20
different parameters can be defined in this menu.
Q1 My Personal Menu
20-21 Setpoint 1
20-93 PID Proportional Gain
20-94 PID Integral Time
How to program the adjustab...