On
Warn.
Alarm
130BP044.10
GLCP keys
Menu keys
The menu keys are divided into functions. The keys below
the display and LEDs are used for parameter set-up,
including choice of display indication during normal
operation.
130BP045.10
Status
Quick
Menu
Main
Menu
Alarm
Log
[Status]
Indicates the status of the adjustable frequency drive
and/or the motor. Three different readouts can be chosen
by pressing the [Status] key:
5 line readouts, 4 line readouts or Smart Logic Control.
Use [Status] for selecting the mode of display or for
changing back to display mode from either the quick
menu mode, the main menu mode or alarm mode. Also
use the [Status] key to toggle single or double readout
mode.
[Quick Menu]
Allows quick set-up of the adjustable frequency drive. The
most common functions can be programmed here.
The [Quick Menu] consists of:
-
Q1: My Personal Menu
-
Q2: Quick Setup
-
Q3: Function Setups
-
Q5: Changes Made
-
Q6: Loggings
The Function set-up provides quick and easy access to all
parameters required for the majority of water and
wastewater applications including variable torque, constant
torque, pumps, dosing pumps, well pumps, booster
pumps, mixer pumps, aeration blowers and other pump
and fan applications. Among other features, it also includes
parameters for selecting which variables to display on the
LCP, digital preset speeds, scaling of analog references,
closed-loop single zone and multi-zone applications and
specific functions related to water and wastewater
applications.
The Quick Menu parameters can be accessed immediately
unless a password has been created via par. 0-60, 0-61,
0-65 or 0-66.
It is possible to switch directly between Quick Menu mode
and Main Menu mode.
[Main Menu]
is used for programming all parameters.
The Main Menu parameters can be accessed immediately
unless a password has been created via par. 0-60, 0-61,
0-65 or 0-66. For the majority of water and wastewater
applications it is not necessary to access the main menu
parameters, but instead the quick menu, quick set-up and
function set-ups provide the simplest and quickest access
to the typical required parameters.
It is possible to switch directly between Main Menu mode
and Quick Menu mode.
Parameter shortcut can be carried out by pressing down
the
[Main Menu]
key for 3 seconds. The parameter shortcut
allows direct access to any parameter.
[Alarm Log]
displays an alarm list of the five latest alarms (numbered
A1-A5). To obtain additional details about an alarm, use
the arrow keys to navigate to the alarm number and press
[OK]. Information is displayed about the condition of the
adjustable frequency drive before it enters alarm mode.
[Back]
reverts to the previous step or layer in the navigation
structure.
[Cancel]
the last change or command will be canceled as long as
the display has not been changed.
[Info]
displays information about a command, parameter, or
function in any display window. [Info] provides detailed
information when needed.
Exit Info mode by pressing either [Info], [Back], or [Cancel].
Back
Cancel
Info
Navigation keys
The four navigation arrows are used to navigate between
the different choices available in [Quick Menu], [Main
Menu] and [Alarm Log]. Use the keys to move the cursor.
[OK]
is used for choosing a parameter marked by the cursor
and for enabling the change of a parameter.
How to operate the adjustab...
VLT AQUA 12-Pulse High Power Instruction Manual
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark
5-3
5
5