6-50 Terminal 42 Output
Option:
Function:
Select the function of Terminal 42 as
an analog current output. A motor
current of 20 mA corresponds to
I
max
.
[0]
*
No operation
[100]
Output frequency
0–100 Hz, (0–20 mA)
[101]
Reference
Minimum reference - Maximum
reference, (0–20 mA)
[102]
Feedback
-200% to +200% of
20-14 Maximum
Reference/Feedb.
, (0–20 mA)
[103]
Motor current
0 - Inverter Max. Current (
16-37 Inv.
Max. Current
), (0–20 mA)
[104]
Torque rel to limit
0 - Torque limit (
4-16 Torque Limit
Motor Mode
), (0–20 mA)
[105]
Torq relate to
rated
0 - Motor rated torque, (0–20 mA)
[106]
Power
0 - Motor rated power, (0–20 mA)
[107]
*
Speed
0 - Speed High Limit (
and
4-14 Motor Speed High Limit [Hz]
), (0–
20 mA)
[113]
Ext. Closed-loop 1
0–100%, (0–20 mA)
[114]
Ext. Closed-loop 2
0–100%, (0–20 mA)
[115]
Ext. Closed-loop 3
0–100%, (0–20 mA)
[130]
Output freq.
4-20mA
0–100 Hz
[131]
Reference 4-20mA
Minimum Reference - Maximum
Reference
[132]
Feedback 4-20mA
-200% to +200% of
20-14 Maximum
Reference/Feedb.
[133]
Motor cur. 4-20mA 0 - Inverter Max. Current (
16-37 Inv.
Max. Current
)
[134]
Torq.% lim 4-20
mA
0 - Torque limit (
4-16 Torque Limit
Motor Mode
)
[135]
Torq.% nom 4-20
mA
0 - Motor rated torque
[136]
Power 4-20mA
0 - Motor rated power
[137]
Speed 4-20mA
0 - Speed High Limit (F-17 and F-15)
[139]
Bus ctrl.
0–100%, (0–20 mA)
[140]
Bus ctrl. 4-20 mA
0 - 100%
[141]
Bus ctrl t.o.
0–100%, (0–20 mA)
[142]
Bus ctrl 4-20mA
t.o.
0 - 100%
6-50 Terminal 42 Output
Option:
Function:
[143]
Ext. Closed-loop 1
4-20 mA
0 - 100%
[144]
Ext. Closed-loop 2
4-20 mA
0 - 100%
[145]
Ext. Closed-loop 3
4-20 mA
0 - 100%
NOTE!
Values for setting the minimum reference are found in
open-loop
and for closed-loop
20-13 Minimum Reference/Feedb.
- values for maximum
reference for open-loop are found in
3-03 Maximum
Reference
and for closed-loop
20-14 Maximum Reference/
Feedb.
.
6-51 Terminal 42 Output Min Scale
Range:
Function:
0.00 %
*
[0.00 - 200.00 %]
6-52 Terminal 42 Output Max Scale
Range:
Function:
100.00 %
*
[0.00 - 200.00 %]
20
mA / desired maximum current × 100 %
i.e. 10mA : 20 mA
10
mA × 100 % = 200 %
EXAMPLE 1:
Variable value= OUTPUT FREQUENCY, range = 0–100 Hz
Range needed for output = 0–50 Hz
Output signal 0 or 4 mA is needed at 0 Hz (0% of range) -
set
6-51 Terminal 42 Output Min Scale
to 0%
Output signal 20 mA is needed at 50 Hz (50% of range) -
set
6-52 Terminal 42 Output Max Scale
to 50%
0/4 mA
20 mA
50%
100%
0%
50Hz
100Hz
0Hz
130BA858.10
EXAMPLE 2:
Variable= FEEDBACK, range= -200% to +200%
Range needed for output= 0–100%
How to program the adjustab...