0-20 Display Line 1.1 Small
Option:
Function:
[1005]
Readout Transmit
Error Counter
View the number of CAN control
transmission errors since the last
power-up.
[1006]
Readout Receive
Error Counter
View the number of CAN control
receipt errors since the last power-
up.
[1007]
Readout Bus Off
Counter
View the number of Bus Off
events since the last power-up.
[1013]
Warning Parameter
View a DeviceNet-specific warning
word. One separate bit is assigned
to every warning.
[1230]
[1472]
[1473]
[1474]
[1501]
Running Hours
View the number of running hours
of the motor.
[1502]
kWh Counter
View the line power consumption
in kWh.
[1600]
Control Word
View the control word sent from
the adjustable frequency drive via
the serial communication port in
hex code.
[1601]
*
Reference [Unit]
Total reference (sum of digital/
analog/preset/bus/freeze ref./catch
up and slow-down) in selected
unit.
[1602]
Reference %
Total reference (sum of digital/
analog/preset/bus/freeze ref./catch
up and slow-down) in percent.
[1603]
Status Word
Present status word
[1605]
Main Actual Value
[%]
One or more warnings in a Hex
code
[1609]
Custom Readout
View the user-defined readouts as
defined in
0-30 Custom Readout
Unit
,
0-31 Custom Readout Min
Value
and
0-32 Custom Readout
Max Value
.
[1610]
Power [kW]
Actual power consumed by the
motor in kW.
[1611]
Power [hp]
Actual power consumed by the
motor in HP.
[1612]
Motor voltage
Voltage supplied to the motor.
[1613]
Frequency
Motor frequency, i.e., the output
frequency from the adjustable
frequency drive in Hz.
0-20 Display Line 1.1 Small
Option:
Function:
[1614]
Motor Current
Phase current of the motor
measured as effective value.
[1615]
Frequency [%]
Motor frequency, i.e., the output
frequency from the adjustable
frequency drive in percent.
[1616]
Torque [Nm]
Present motor load as a
percentage of the rated motor
torque.
[1617]
*
Speed [RPM]
Speed in RPM (revolutions per
minute), i.e., the motor shaft
speed in closed-loop based on the
entered motor nameplate data,
the output frequency and the load
on the adjustable frequency drive.
[1618]
Motor Thermal
Thermal load on the motor,
calculated by the ETR function.
See also parameter group 1-9*
Motor Temperature.
[1619]
KTY sensor
temperature
[1620]
Motor Angle
[1622]
Torque [%]
Shows the actual torque
produced, in percentage.
[1625]
[1630]
DC Link Voltage
Intermediate circuit voltage in the
adjustable frequency drive.
[1632]
Brake Energy /s
Present braking energy transferred
to an external brake resistor.
Stated as an instantaneous value.
[1633]
Brake Energy /2
min
Braking energy transferred to an
external brake resistor. The mean
power is calculated continuously
for the most recent 120 seconds.
[1634]
Heatsink Temp.
Present heatsink temperature of
the adjustable frequency drive.
The cut-out limit is 203°F ±41°F
[95°C ± 5°C]; cutting back in
occurs at 158°F ±41°F [70°C ±
5°C].
[1635]
Inverter Thermal
Percentage load of the inverters
[1636]
Inv. Nom. Current
Nominal current of the adjustable
frequency drive.
[1637]
Inv. Max. Current
Maximum current of the
adjustable frequency drive.
[1638]
SL Controller State
State of the event executed by
the control
How to program the adjustab...