Line Power Supply 6 x 380–480V AC
650 HP
750 HP
900 HP
1000 HP
1200 HP
1400 HP
Typical Shaft output at 400 V
[kW]
500
560
630
710
800
1000
Typical Shaft output at 460 V
[HP]
650
750
900
1000
1200
1350
Typical Shaft output at 480 V
[kW]
560
630
710
800
1000
1100
IP21/Nema 1 and IP54/Nema
12 Drive Types without/with
options cabinet
F10/F11
F10/F11
F10/F11
F10/F11
F12/F13
F12/F13
Output current
Continuous
(at 400 V) [A]
880
990
1120
1260
1460
1720
Intermittent (60 sec overload)
(at 400 V) [A]
968
1089
1232
1386
1606
1892
Continuous
(at 460/ 480 V) [A]
780
890
1050
1160
1380
1530
Intermittent (60 sec overload)
(at 460/ 480 V) [A]
858
979
1155
1276
1518
1683
Continuous KVA
(at 400 V) [KVA]
610
686
776
873
1012
1192
Continuous KVA
(at 460 V) [KVA]
621
709
837
924
1100
1219
Continuous KVA
(at 480 V) [KVA]
675
771
909
1005
1195
1325
Max. input current
Continuous
(at 400 V) [A]
857
964
1090
1227
1422
1675
Continuous (at 460/ 480 V) [A]
759
867
1022
1129
1344
1490
Max. cable size,motor [mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
12x150
(12x300 mcm)
Max. cable size, line power
[mm
2
(AWG
2)
)]
6x120
(6x250 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
4x185
(4x350 mcm)
6x185
(6x350 mcm)
Max. external electrical fuses
[A] 1
900
1500
Estimated power loss
at 400 V [W]
4)
10647
12338
13201
15436
18084
20358
Estimated power loss
at 460 V [W]
9414
11006
12353
14041
17137
17752
max. added losses A1 RFI, CB
or Disconnect, & contactor
963
1054
1093
1230
2280
2541
Max. panel options losses
400
Weight,
Unit Size IP21, IP 54 [kg]
1004/ 1299
1004/ 1299
1004/ 1299
1004/ 1299
1246/ 1541
1246/ 1541
Weight Rectifier Module [kg]
102
102
102
102
136
136
Weight Inverter Module [kg]
102
102
102
136
102
102
Efficiency
4)
0.98
Output frequency
0–600Hz
Heatsink overtemp. trip
203°F [95°C]
Power card ambient trip
154.4°F [68°C]
* Heavy Duty = 160% torque during 60 sec., Light Duty = 110% torque during 60 sec.
General Specifications
VLT AQUA 12-Pulse High Power Instruction Manual
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark
7-7