22-32 Low Speed [RPM]
Range:
Function:
0 RPM
*
[0 - par.
22-36 RPM]
To be used if
0-02 Motor Speed Unit
has
been set for RPM (parameter not visible if
Hz selected).
Set used speed to the 50% level.
This function is used for storing values
needed to tune No-Flow Detection.
22-33 Low Speed [Hz]
Range:
Function:
0 Hz
*
[0.0 - par.
22-37 Hz]
To be used if
0-02 Motor Speed Unit
has
been set for Hz (parameter not visible if
RPM selected).
Set used speed to the 50% level.
The function is used for storing values
needed to tune No-Flow Detection.
22-34 Low Speed Power [kW]
Range:
Function:
0 kW
*
[0.00 -
0.00 kW]
To be used if
0-03 Regional Settings
has
been set for International (parameter not
visible if North America selected).
Set power consumption to 50% speed level.
This function is used for storing values
needed to tune No-Flow Detection.
22-35 Low Speed Power [HP]
Range:
Function:
0 hp
*
[0.00 -
0.00 hp]
To be used if
0-03 Regional Settings
has been
set for North America (parameter not visible
if International selected).
Set power consumption to 50% speed level.
This function is used for storing values
needed to tune No-Flow Detection.
22-36 High Speed [RPM]
Range:
Function:
0 RPM
*
[0 - par.
4-13 RPM]
To be used if
0-02 Motor Speed Unit
has
been set for RPM (parameter not visible if
Hz selected).
Set used speed for the 85% level.
The function is used for storing values
needed to tune No-Flow Detection.
22-37 High Speed [Hz]
Range:
Function:
0.0 Hz
*
[0.0 - par.
4-14 Hz]
To be used if
0-02 Motor Speed Unit
has
been set for Hz (parameter not visible if
RPM selected).
Set used speed for the 85% level.
22-37 High Speed [Hz]
Range:
Function:
The function is used for storing values
needed to tune No-Flow Detection.
22-38 High Speed Power [kW]
Range:
Function:
0 kW
*
[0.00 -
0.00 kW]
To be used if
0-03 Regional Settings
has
been set for International (parameter not
visible if North America selected).
Set power consumption to 85% speed level.
This function is used for storing values
needed to tune No-Flow Detection.
22-39 High Speed Power [HP]
Range:
Function:
0 hp
*
[0.00 -
0.00 hp]
To be used if
0-03 Regional Settings
has been
set for North America (parameter not visible
if International selected).
Set power consumption to 85% speed level.
This function is used for storing values
needed to tune No-Flow Detection.
22-40 Minimum Run Time
Range:
Function:
10 s
*
[0 - 600 s]
22-41 Minimum Sleep Time
Range:
Function:
10 s
*
[0 - 600 s] Set the desired minimum time for staying in
sleep mode. This will override any wake-up
conditions.
22-42 Wake-up Speed [RPM]
Range:
Function:
0 RPM
*
[par. 4-11
- par. 4-13
RPM]
To be used if
0-02 Motor Speed Unit
has
been set for RPM (parameter not visible if
Hz selected). Only to be used if
is set for open-
loop and speed reference is applied by an
external controller.
Set the reference speed at which sleep
mode should be canceled.
How to program the adjustab...