No.
Description
Warning
Alarm/Trip
Alarm/Trip Lock
Parameter Reference
220
Overload Trip
X
244
Heatsink temp
X
X
X
245
Heatsink sensor
X
X
246
Pwr.card supply
X
X
247
Pwr.card temp
X
X
248
Illegal PS config
X
X
250
New spare part
X
251
New Model Number
X
X
Table 8.2 Alarm/Warning Code List
(X) Dependent on parameter
1) Cannot be Auto reset via 14-20 Reset Mode
A trip is the action when an alarm has appeared. The trip will coast the motor and can be reset by pressing the reset
button or make a reset by a digital input (Par. E-1# [1]). The original event that caused an alarm cannot damage the
adjustable frequency drive or cause dangerous conditions. A trip lock is an action that occurs in conjunction with an alarm,
which may cause damage to the adjustable frequency drive or connected parts. A trip lock situation can only be reset by
power cycling.
LED indication
Warning
yellow
Alarm
flashing red
Trip locked
yellow and red
Alarm Word and Extended Status Word
Bit
Hex
Dec
Alarm Word
Warning Word
Extended Status Word
0
00000001
1
Brake Check
Brake Check
Ramping
1
00000002
2
Pwr. Card Temp
Pwr. Card Temp
Auto Tune Running
2
00000004
4
Ground Fault
Ground Fault
Start CW/CCW
3
00000008
8
Ctrl.Card Temp
Ctrl.Card Temp
Slow-down
4
00000010
16
Ctrl. Word TO
Ctrl. Word TO
Catch Up
5
00000020
32
Overcurrent
Overcurrent
Feedback High
6
00000040
64
Torque Limit
Torque Limit
Feedback Low
7
00000080
128
Thrmstr Overld
Thrmstr Overld
Output Current High
8
00000100
256
Motor Elec. OL Over
Motor Elec. OL Over
Output Current Low
9
00000200
512
Inverter Overld.
Inverter Overld.
Output Freq High
10
00000400
1024
DC undervolt
DC undervolt
Output Freq Low
11
00000800
2048
DC overvolt
DC overvolt
Brake Check OK
12
00001000
4096
Short Circuit
DC Voltage Low
Braking Max
13
00002000
8192
Inrush Fault
DC Voltage High
Braking
14
00004000
16384
Mains phs. Loss
Mains phs. Loss
Out of Speed Range
15
00008000
32768
Auto Tune Not OK
No Motor
OVC Active
16
00010000
65536
Live Zero Error
Live Zero Error
17
00020000
131072
Internal Fault
10V low
18
00040000
262144
19
00080000
524288
U phase Loss
20
00100000
1048576
V phase Loss
21
00200000
2097152
W phase Loss
Speed Limit
22
00400000
4194304
Fieldbus Fault
Fieldbus Fault
23
00800000
8388608
24 V Supply Low
24V Supply Low
24
01000000
16777216
Mains Failure
Line Failure
25
02000000
33554432
1.8V supply low
Current Limit
26
04000000
67108864
Brake Resistor
Low Temp
27
08000000
134217728
Brake IGBT
Voltage Limit
28
10000000
268435456
Option Change
Unused
29
20000000
536870912
Drive Restored to Factory
Settings
Unused
30
40000000
1073741824
Unused
Table 8.3 Description of Alarm Word, Warning Word and Extended Status Word
The alarm words, warning words and extended status words can be read out via serial bus or optional serial communication
bus for diagnosis. See also
16-90 Alarm Word
,
16-92 Warning Word
and
16-94 Ext. Status Word
.
Troubleshooting