6.3.22 Analog I/O Option MCB 109 26-**
Par.
No. #
Parameter description
Default value
4 set-up
Change during
operation
Conver-
sion index
Type
26-0* Analog I/O Mode
26-00
Terminal X42/1 Mode
[1] Voltage
All set-ups
TRUE
-
Uint8
26-01
Terminal X42/3 Mode
[1] Voltage
All set-ups
TRUE
-
Uint8
26-02
Terminal X42/5 Mode
[1] Voltage
All set-ups
TRUE
-
Uint8
26-1* Analog Input X42/1
26-10
Terminal X42/1 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
26-11
Terminal X42/1 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
26-14
Term. X42/1 Low Ref./Feedb. Value
0.000 N/A
All set-ups
TRUE
-3
Int32
26-15
Term. X42/1 High Ref./Feedb. Value
100.000 N/A
All set-ups
TRUE
-3
Int32
26-16
Term. X42/1 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
26-17
Term. X42/1 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
26-2* Analog Input X42/3
26-20
Terminal X42/3 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
26-21
Terminal X42/3 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
26-24
Term. X42/3 Low Ref./Feedb. Value
0.000 N/A
All set-ups
TRUE
-3
Int32
26-25
Term. X42/3 High Ref./Feedb. Value
100.000 N/A
All set-ups
TRUE
-3
Int32
26-26
Term. X42/3 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
26-27
Term. X42/3 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
26-3* Analog Input X42/5
26-30
Terminal X42/5 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
26-31
Terminal X42/5 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
26-34
Term. X42/5 Low Ref./Feedb. Value
0.000 N/A
All set-ups
TRUE
-3
Int32
26-35
Term. X42/5 High Ref./Feedb. Value
100.000 N/A
All set-ups
TRUE
-3
Int32
26-36
Term. X42/5 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
26-37
Term. X42/5 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
26-4* Analog Out X42/7
26-40
Terminal X42/7 Output
[0] No operation
All set-ups
TRUE
-
Uint8
26-41
Terminal X42/7 Min. Scale
0.00%
All set-ups
TRUE
-2
Int16
26-42
Terminal X42/7 Max. Scale
100.00%
All set-ups
TRUE
-2
Int16
26-43
Terminal X42/7 Bus Control
0.00%
All set-ups
TRUE
-2
N2
26-44
Terminal X42/7 Timeout Preset
0.00%
1 set-up
TRUE
-2
Uint16
26-5* Analog Out X42/9
26-50
Terminal X42/9 Output
[0] No operation
All set-ups
TRUE
-
Uint8
26-51
Terminal X42/9 Min. Scale
0.00%
All set-ups
TRUE
-2
Int16
26-52
Terminal X42/9 Max. Scale
100.00%
All set-ups
TRUE
-2
Int16
26-53
Terminal X42/9 Bus Control
0.00%
All set-ups
TRUE
-2
N2
26-54
Terminal X42/9 Timeout Preset
0.00%
1 set-up
TRUE
-2
Uint16
26-6* Analog Out X42/11
26-60
Terminal X42/11 Output
[0] No operation
All set-ups
TRUE
-
Uint8
26-61
Terminal X42/11 Min. Scale
0.00%
All set-ups
TRUE
-2
Int16
26-62
Terminal X42/11 Max. Scale
100.00%
All set-ups
TRUE
-2
Int16
26-63
Terminal X42/11 Bus Control
0.00%
All set-ups
TRUE
-2
N2
26-64
Terminal X42/11 Timeout Preset
0.00%
1 set-up
TRUE
-2
Uint16
How to program the adjustab...
VLT AQUA 12-Pulse High Power Instruction Manual
6-64
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark
6
6