6.3.19 Application Functions 22-**
Par. No.
#
Parameter description
Default value
4 set-up
Change
during
operation
Conver-
sion index
Type
22-0* Miscellaneous
22-00
External Interlock Delay
0 s
All set-ups
TRUE
0
Uint16
22-2* No-Flow Detection
22-20
Low Power Auto Set-up
[0] Off
All set-ups
FALSE
-
Uint8
22-21
Low Power Detection
[0] Disabled
All set-ups
TRUE
-
Uint8
22-22
Low Speed Detection
[0] Disabled
All set-ups
TRUE
-
Uint8
22-23
No-Flow Function
[0] Off
All set-ups
TRUE
-
Uint8
22-24
No-Flow Delay
10 s
All set-ups
TRUE
0
Uint16
22-26
Dry Pump Function
[0] Off
All set-ups
TRUE
-
Uint8
22-27
Dry Pump Delay
10 s
All set-ups
TRUE
0
Uint16
22-3* No-Flow Power Tuning
22-30
No-Flow Power
0.00 kW
All set-ups
TRUE
1
Uint32
22-31
Power Correction Factor
100 %
All set-ups
TRUE
0
Uint16
22-32
Low Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
22-33
Low Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
22-34
Low Speed Power [kW]
ExpressionLimit
All set-ups
TRUE
1
Uint32
22-35
Low Speed Power [HP]
ExpressionLimit
All set-ups
TRUE
-2
Uint32
22-36
High Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
22-37
High Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
22-38
High Speed Power [kW]
ExpressionLimit
All set-ups
TRUE
1
Uint32
22-39
High Speed Power [HP]
ExpressionLimit
All set-ups
TRUE
-2
Uint32
22-4* Sleep Mode
22-40
Minimum Run Time
60 s
All set-ups
TRUE
0
Uint16
22-41
Minimum Sleep Time
30 s
All set-ups
TRUE
0
Uint16
22-42
Wake-up Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
22-43
Wake-up Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
22-44
Wake-up Ref./FB Difference
10 %
All set-ups
TRUE
0
Int8
22-45
Setpoint Boost
0 %
All set-ups
TRUE
0
Int8
22-46
Maximum Boost Time
60 s
All set-ups
TRUE
0
Uint16
22-5* End of Curve
22-50
End of Curve Function
[0] Off
All set-ups
TRUE
-
Uint8
22-51
End of Curve Delay
10 s
All set-ups
TRUE
0
Uint16
22-6* Broken Belt Detection
22-60
Broken Belt Function
[0] Off
All set-ups
TRUE
-
Uint8
22-61
Broken Belt Torque
10 %
All set-ups
TRUE
0
Uint8
22-62
Broken Belt Delay
10 s
All set-ups
TRUE
0
Uint16
22-7* Short Cycle Protection
22-75
Short Cycle Protection
[0] Disabled
All set-ups
TRUE
-
Uint8
22-76
Interval between Starts
start_to_start_
min_on_time
(P2277)
All set-ups
TRUE
0
Uint16
22-77
Minimum Run Time
0 s
All set-ups
TRUE
0
Uint16
How to program the adjustab...