6.3.18 Ext. Closed-loop 21-**
Par. No.
#
Parameter description
Default value
4 set-up
Change during
operation
Conver-
sion index
Type
21-0* Ext. CL Autotuning
21-00
Closed-loop Type
[0] Auto
2 set-ups
TRUE
-
Uint8
21-01
PID Performance
[0] Normal
2 set-ups
TRUE
-
Uint8
21-02
PID Output Change
0.10 N/A
2 set-ups
TRUE
-2
Uint16
21-03
Minimum Feedback Level
-999999.000 N/A
2 set-ups
TRUE
-3
Int32
21-04
Maximum Feedback Level
999999.000 N/A
2 set-ups
TRUE
-3
Int32
21-09
PID Auto Tuning
[0] Disabled
All set-ups
TRUE
-
Uint8
21-1* Ext. CL 1 Ref./Fb.
21-10
Ext. 1 Ref./Feedback Unit
[0]
All set-ups
TRUE
-
Uint8
21-11
Ext. 1 Minimum Reference
0.000 ExtPID1Unit
All set-ups
TRUE
-3
Int32
21-12
Ext. 1 Maximum Reference
100.000 ExtPID1Unit
All set-ups
TRUE
-3
Int32
21-13
Ext. 1 Reference Source
[0] No function
All set-ups
TRUE
-
Uint8
21-14
Ext. 1 Feedback Source
[0] No function
All set-ups
TRUE
-
Uint8
21-15
Ext. 1 Setpoint
0.000 ExtPID1Unit
All set-ups
TRUE
-3
Int32
21-17
Ext. 1 Reference [Unit]
0.000 ExtPID1Unit
All set-ups
TRUE
-3
Int32
21-18
Ext. 1 Feedback [Unit]
0.000 ExtPID1Unit
All set-ups
TRUE
-3
Int32
21-19
Ext. 1 Output [%]
0 %
All set-ups
TRUE
0
Int32
21-2* Ext. CL 1 PID
21-20
Ext. 1 Normal/Inverse Control
[0] Normal
All set-ups
TRUE
-
Uint8
21-21
Ext. 1 Proportional Gain
0.50 N/A
All set-ups
TRUE
-2
Uint16
21-22
Ext. 1 Integral Time
20.00 s
All set-ups
TRUE
-2
Uint32
21-23
Ext. 1 Differentiation Time
0.00 s
All set-ups
TRUE
-2
Uint16
21-24
Ext. 1 Dif. Gain Limit
5.0 N/A
All set-ups
TRUE
-1
Uint16
21-3* Ext. CL 2 Ref./Fb.
21-30
Ext. 2 Ref./Feedback Unit
[0]
All set-ups
TRUE
-
Uint8
21-31
Ext. 2 Minimum Reference
0.000 ExtPID2Unit
All set-ups
TRUE
-3
Int32
21-32
Ext. 2 Maximum Reference
100.000 ExtPID2Unit
All set-ups
TRUE
-3
Int32
21-33
Ext. 2 Reference Source
[0] No function
All set-ups
TRUE
-
Uint8
21-34
Ext. 2 Feedback Source
[0] No function
All set-ups
TRUE
-
Uint8
21-35
Ext. 2 Setpoint
0.000 ExtPID2Unit
All set-ups
TRUE
-3
Int32
21-37
Ext. 2 Reference [Unit]
0.000 ExtPID2Unit
All set-ups
TRUE
-3
Int32
21-38
Ext. 2 Feedback [Unit]
0.000 ExtPID2Unit
All set-ups
TRUE
-3
Int32
21-39
Ext. 2 Output [%]
0 %
All set-ups
TRUE
0
Int32
21-4* Ext. CL 2 PID
21-40
Ext. 2 Normal/Inverse Control
[0] Normal
All set-ups
TRUE
-
Uint8
21-41
Ext. 2 Proportional Gain
0.50 N/A
All set-ups
TRUE
-2
Uint16
21-42
Ext. 2 Integral Time
20.00 s
All set-ups
TRUE
-2
Uint32
21-43
Ext. 2 Differentiation Time
0.00 s
All set-ups
TRUE
-2
Uint16
21-44
Ext. 2 Dif. Gain Limit
5.0 N/A
All set-ups
TRUE
-1
Uint16
How to program the adjustab...
VLT AQUA 12-Pulse High Power Instruction Manual
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark
6-57
6