el
Operation keys
for local control are found at the bottom of the control
panel.
130BP046.10
Hand
on
Off
Auto
on
Reset
[Hand on]
enables control of the adjustable frequency drive via the
GLCP. [Hand on] also starts the motor, and makes it
possible to give the motor speed reference using the
arrow keys. The key can be
Enabled
[1] or
Disabled
[0] via
par.
0-40 [Hand on] Key on LCP.
The following control signals will still be active when
[Hand on] is activated:
•
[Hand on] - [Off] - [Auto on]
•
Reset
•
Coasting stop inverse (motor coasting to stop)
•
Reversing
•
Set-up select lsb - Set-up select msb
•
Stop command from serial communication
•
Quick stop
•
DC brake
External stop signals activated by means of control signals
or a serial bus will override a “start” command via the LCP.
[Off]
stops the connected motor. The key can be
Enabled
[1] or
Disabled
[0] via par.
0-41 [Off] key on LCP.
If no external
stop function is selected and the [Off] key is inactive, the
motor can only be stopped by disconnecting the line
power supply.
[Auto on]
enables the adjustable frequency drive to be controlled via
the control terminals and/or serial communication. When a
start signal is applied on the control terminals and/or the
bus, the adjustable frequency drive will start. The key can
be
Enabled
[1] or
Disabled
[0] via par.
0-42 [Auto on] key on
LCP.
An active HAND-OFF-AUTO signal via the digital inputs has
higher priority than the control keys [Hand on] – [Auto on].
[Reset]
is used for resetting the adjustable frequency drive after an
alarm (trip). The key can be
Enabled
[1] or
Disabled
[0] via
par. 0-43
Reset Keys on LCP
.
The parameter shortcut
can be carried out by holding down the [Main Menu] key
for 3 seconds. The parameter shortcut allows direct access
to any parameter.
5.1.3 Changing Data
1.
Press the [Quick Menu] or [Main Menu] key.
2.
Use [
▲
] and [
▼
] keys to find parameter group to
edit.
3.
Press [OK] key.
4.
Use [
▲
] and [
▼
] keys to find parameter to edit.
5.
Press [OK] key.
6.
Use [
▲
] and [
▼
] keys to select correct parameter
setting. Or, to move to digits within a number,
use the left or right arrow keys. Cursor indicates
digit selected to change. [
▲
] key increases the
value, [
▼
] key decreases the value.
7.
Press the [Cancel] key to disregard the change, or
press the [OK] key to accept the change and
enter the new setting.
5.1.4 Changing a Text Value
If the selected parameter is a text value, it can be changed
by using the up/down navigation keys.
The up key increases the value, and the down key
decreases the value. Place the cursor on the value to be
saved and press [OK].
130BP068.10
740RPM
0 -01 Language
[0] English
10.64 A
1 [1]
0-0*
Basic Settings
Figure 5.1 Display example.
How to operate the adjustab...
VLT AQUA 12-Pulse High Power Instruction Manual
5-4
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark
5