22-80 Flow Compensation
Option:
Function:
[0]
*
Disabled [0]
Disabled
: Setpoint compensation not active.
[1]
Enabled [1]
Enabled
: Setpoint compensation is active.
Enabling this parameter allows the Flow
Compensated Setpoint operation.
22-81 Square-linear Curve Approximation
Range:
Function:
100 %
*
[0 - 100 %]
NOTE!
Not visible when running in cascade.
Control Curve
(head)
(flow)
H
Q
130BA388.11
100%
P22-81 0%
22-82 Work Point Calculation
Option:
Function:
Example 1: Speed at system design working point
is known:
P22-83/
P22-84
P22-87
A
130BA385.11
P22-85/22-86
Control Curve
HMIN
HDESIGNSetpoint
nR
ATED_f
RA
TED
nDESIGN-fDESIGN
H(head)
From the data sheet showing characteristics for
the specific equipment at different speeds, simply
reading across from the H
DESIGN
point and the
Q
DESIGN
point allows us to find point A, which is
the system design working point. The pump
characteristics at this point should be identified
and the associated speed programmed. Closing
the valves and adjusting the speed until H
MIN
has
been achieved allows the speed at the no flow
point to be identified.
Adjustment of
22-81 Square-linear Curve Approxi-
then allows the shape of the control curve
to be adjusted infinitely.
22-82 Work Point Calculation
Option:
Function:
Example 2:
Speed at system design working point is not
known: Where the speed at system design
working point is unknown, another reference point
on the control curve needs to be determined by
means of the data sheet. By looking at the curve
for the rated speed and plotting the design
pressure (H
DESIGN
, Point C), the flow at that
pressure Q
RATED
can be determined. Similarly, by
plotting the design flow (Q
DESIGN
, Point D), the
pressure H
D
at that flow can be determined.
Knowing these two points on the pump curve,
along with H
MIN
described above, allows the
adjustable frequency drive to calculate the
reference point B and thus to plot the control
curve that will also include the system design
working point A.
Setpoint
Control Curve
nD
ES
IG
N
nR
AT
ED
(head)
H
H RATED
P22-88
Q DESIGN
P22-89
H MIN
P22-83/
P22-84
P22-87
D B
C
A
Q RATED
P22-90
Q
H DESIGN
130BA387.11
[0]
*
Disabled
Disabled
[0]: Work point calculation is not active.
To be used if speed at design point is known (see
table above).
[1] Enabled
Enabled [1]
: Work point calculation is active.
Enabling this parameter allows the calculation of
the unknown System Design Working Point at
50/60 Hz speed, from the input data set in
,
22-87 Pressure at No-Flow Speed
,
22-89 Flow at Design
Point
and
.
22-84 Speed at No-Flow [Hz]
Range:
Function:
50.0
Hz
*
[0.0 -
par. 22-86
Hz]
Resolution 0.033 Hz.
The speed of the motor at which flow has
effectively stopped and minimum pressure
H
MIN
is achieved should be entered here in
Hz. Alternatively, the speed in RPM can be
entered in
. If it
has been decided to use Hz in
0-02 Motor
Speed Unit
, then
should also be used. Closing the valves
and reducing the speed until minimum
pressure H
MIN
is achieved will determine this
value.
How to program the adjustab...
VLT AQUA 12-Pulse High Power Instruction Manual
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark
6-29