Line Power Supply 3 x 525–690V AC
Typical Shaft output at 550 V [kW]
560
670
750
Typical Shaft output at 575 V [HP]
750
950
1050
Typical Shaft output at 690 V [kW]
710
800
900
IP21/Nema 1 and IP54/Nema 12 Drive
Types without/with options cabinet
F10/F11
F10/F11
F10/F11
Output current
Continuous
(at 550 V) [A]
763
889
988
Intermittent (60 sec overload)
(at 550 V) [A]
839
978
1087
Continuous
(at 575/690 V) [A]
730
850
945
Intermittent (60 sec overload)
(at 575/690 V) [A]
803
935
1040
Continuous KVA
(at 550 V) [KVA]
727
847
941
Continuous KVA
(at 690 V) [KVA]
872
1016
1129
Max. input current
Continuous
(at 550 V) [A]
743
866
962
Continuous
(at 575 V) [A]
711
828
920
Continuous
(at 690 V) [A]
711
828
920
Max. cable size, motor [mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
Max. cable size, line power [mm
2
(AWG
2)
)]
6x120
(6x250 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
4x185
(4x350 mcm)
Max. external electrical fuses [A] 1
900
Estimated power loss
at 600 V [W]
4)
10771
12272
13835
Estimated power loss
at 690V [W]
4)
11315
12903
14533
63/64 Max added losses CB or Disconnect
& Contactor
427
532
615
Max panel options losses
400
Weight,
Unit Size IP21, IP 54 [kg]
1004/ 1299
1004/ 1299
1004/ 1299
Weight, Rectifier Module [kg]
102
102
102
Weight, Inverter Module [kg]
102
102
136
Efficiency
4)
0.98
Output frequency
0–500 Hz
Heatsink overtemp. trip
185°F [85°C]
Power card ambient trip
154.4°F [68°C]
* Heavy Duty = 160% torque during 60 sec., Light Duty = 110% torque during 60 sec.
1) For type of fuse, see section Fuses.
2) American Wire Gauge.
3) Measured using 16.4 ft. [5 m] shielded motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be /-15% (tolerance relates to
variety in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to
the power loss in the adjustable frequency drive and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
LCP and typical control card power consumptions are included. Further options and customer load may add up to
30W to the losses. (Though typical, only 4 W extra for a fully loaded control card, or options for slot A or slot B,
each.)
Although measurements are made with state of the art equipment, some measurement inaccuracy must be
allowed for (+/-5%).
General Specifications
VLT AQUA 12-Pulse High Power Instruction Manual
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark
7-9
7
7