CAUTION
Leakage Current
The ground leakage current from the adjustable frequency
drive exceeds 3.5 mA. To ensure that the ground cable has
a good mechanical connection to the ground connection
(terminal 95), the cable cross-section must be at least 0.016
in
2
[10 mm
2
] or 2 rated ground wires terminated
separately. For proper grounding for EMC, see section
Grounding
in the
How to Install
chapter.
Residual Current Device
The drive can cause DC current in the protective
conductor. Where a residual current device (RCD) is used
for extra protection, only an RCD of Type B (time delayed)
shall be used on the supply side of this product.
Protective grounding of the adjustable frequency drive and
the use of RCDs must always follow national and local
regulations.
2.1.4 Before Commencing Repair Work
1.
Disconnect the adjustable frequency drive from
line power.
2.
Disconnect DC bus terminals 88 and 89 from load
share applications
3.
Wait for the discharge of the DC link. See period
of time on the warning label.
4.
Remove motor cable
2.1.5 Avoid Unintended Start
While the adjustable frequency drive is connected to line
power, the motor can be started/stopped using digital
commands, bus commands, references or via the keypad::
•
Disconnect the adjustable frequency drive from
line power whenever personal safety consider-
ations make it necessary to avoid an unintended
start.
•
To avoid unintended start, always activate the
[OFF] key before changing parameters.
•
An electronic fault, temporary overload, a fault in
the line power supply, or lost motor connection
may cause a stopped motor to start. The
adjustable frequency drive with safe stop
provides protection against unintended start, if
Safe Stop Terminal 37 is deactivated or discon-
nected.
2.1.6 Safe Stop
The can perform the safety function
Safe Torque Off
(As
defined by draft CD IEC 61800-5-2) or
Stop Category 0
(as
defined in EN 60204-1).
It is designed and approved suitable for the requirements
of Safety Category 3 in EN 954-1. This functionality is called
Safe Stop. Prior to integration and use of Safe Stop in an
installation, a thorough risk analysis on the installation
must be carried out in order to determine whether the
Safe Stop functionality and safety category are appropriate
and sufficient. In order to install and use the Safe Stop
function in accordance with the requirements of Safety
Category 3 in EN 954-1, the related information and
instructions of the Design Guide must be followed! The
information and instructions of the Instruction Manual are
not sufficient for a correct and safe use of the safe stop
functionality!
2.1.7 Safe Stop Installation
To carry out an installation of a Category 0 Stop
(EN60204) in conformity with Safety Category 3 (EN954-1),
follow these instructions:
1.
The bridge (jumper) between Terminal 37 and
24V DC must be removed. Cutting or breaking
the jumper is not sufficient. Remove it entirely to
avoid short-circuiting. See jumper on
.
2.
Connect terminal 37 to 24 V DC by a short
circuit-protected cable. The 24 V DC voltage
supply must be interruptible by an EN954-1
category 3 circuit interrupt device. If the interrupt
device and the are placed in the same installation
panel, you can use an non-shielded cable instead
of a shielded one.
37
12
130B
T314.10
Figure 2.1 Bridge jumper between terminal 37 and 24 VDC
shows a Stopping Category 0 (EN 60204-1) with
safety Category 3 (EN 954-1). The circuit interrupt is caused
Safety
VLT AQUA 12-Pulse High Power Instruction Manual
2-2
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark
2
2