6.1.4 Q2 Quick Set-up
The parameters in Q2 Quick Set-up are the basic
parameters which are always needed to set up the
adjustable frequency drive for operation.
Q2 Quick Set-up
Parameter number and name
Unit
0-01 Language
1-20 Motor Power
kW
1-22 Motor Voltage
V
1-23 Motor Frequency
Hz
1-24 Motor Current
A
1-25 Motor Nominal Speed
RPM
3-41 Ramp 1 Ramp-up Time
s
3-42 Ramp 1 Ramp-down Time
s
4-11 Motor Speed Low Limit
RPM
4-13 Motor Speed High Limit
RPM
1-29 Automatic Motor
Adaptation (AMA)
6.1.5 Q3 Function Setups
The Function Setup provides quick and easy access to all
parameters required for the majority of water and
wastewater applications including variable torque, constant
torque, pumps, dosing pumps, well pumps, booster
pumps, mixer pumps, aeration blowers and other pump
and fan applications. Among other features, it also includes
parameters for selecting which variables to display on the
LCP, digital preset speeds, scaling of analog references,
closed-loop single zone and multi-zone applications and
specific functions related to water and wastewater
applications.
How to access Function Setups - example:
28.8%
14.4Hz
Auto Remote Running
5.66A
2.63 kW
0 kWh
1 (1)
130
BT110.11
Status
Figure 6.2 Step 1: Turn on the adjustable frequency drive (on
LED lights).
130B
T111.10
Q1 My Personal Menu
Q2 Quick Set-up
Q3 Function Set-ups
Q5 Changes Made
13.7% 13.0A 1(1)
Quick Menus
Figure 6.3 Step 2: Press the [Quick Menus] button (Quick Menus
choices appear).
130B
T112.10
Q1 My Personal Menu
Q2 Quick Set-up
Q3 Function Set-ups
Q5 Changes Made
69.3% 5.20A 1(1)
Quick Menus
Figure 6.4 Step 3: Use the up/down navigation keys to scroll
down to Function Setups. Press [OK].
130BA500.10
1190 RPM
Q3 - 1 General Settings
Q3 - 2 Open-loop Settings
Q3 - 3 Closed-loop Settings
0.000
1 (1)
Q3
Function Set-ups
Figure 6.5 Step 4: Function Setups choices appear. Choose 03-1
General Settings
. Press [OK].
130BA501.10
0.000 rpm
Q3 - 10 Clock Settings
Q3 - 11 Display Settings
Q3 - 12 Analog Output
Q3 - 13 Relays
0.000
1 (1)
Q3-1
General Settings
Figure 6.6 Step 5: Use the up/down navigation keys to scroll
down to, e.g., 03-12
Analog Outputs
. Press [OK].
130BA502.10
0.000 rpm
6 - 50 Terminal 42 Output
(100) Output frequency
0.000
1 (1)
Q3-12
Analog Output
Figure 6.7 Step 6: Choose parameter 6-50
Terminal 42 Output
.
Press [OK].
130BA503.10
0.000 rpm
6 - 50 Terminal 42 Output
(107) Speed
0.000
1 (1)
Q3-12
Analog Output
Figure 6.8 Step 7: Use the up/down navigation keys to select
between the different choices. Press [OK].
How to program the adjustab...