NOTE!
•
For the best results of the adjustable frequency
drive, run Auto Tune on a cold motor
•
Auto Tune cannot be performed while the motor
is running.
NOTE!
Avoid generating external torque during Auto Tune.
NOTE!
If one of the settings in parameter group P-## Motor Data
is changed,
1-30 Stator Resistance (Rs)
to
1-39 Motor Poles
,
the advanced motor parameters will return to default
setting.
This parameter cannot be adjusted while the motor is
running.
NOTE!
Full Auto Tune should be run without filter only while
reduced Auto Tune should be run with filter.
6.2.3 3-0* Reference Limits
3-10 Preset Reference
Array [8]
Range:
Function:
0.00 %
*
[-100.00 - 100.00 %]
P3-03
P3-02
0
50
100%
P3-10
130BB036.10
3-41 Ramp 1 Ramp-up Time
Range:
Function:
10.00 s
*
[1.00 -
3600.00 s]
Enter the accel time, i.e., the
acceleration time from 0 RPM to
. Choose a
accel time such that the output current
does not exceed the current limit in
4-18 Current Limit
during ramping. See
decel time in
.
par
.
F
− 07 =
t
acc
×
n
norm
par
.
P
− 06
ref
rpm
s
3-42 Ramp 1 Ramp-down Time
Range:
Function:
20.00 s
*
[1.00 -
3600.00 s]
Enter the decel time, i.e., the deceleration
time from
to 0
RPM. Choose a decel time such that no
overvoltage arises in the inverter due to
regenerative operation of the motor, and
such that the generated current does not
exceed the current limit set in
4-18 Current Limit
. See accel time in
.
par
.
F
− 08 =
t
dec
×
n
norm
par
.
P
− 06
ref
rpm
s
3-84 Initial Ramp Time
Range:
Function:
0.00 s
*
[0.00–
60.00 s]
Enter the initial ramp-up time from zero
speed to Motor Speed Low Limit,
or
4-12 Motor Speed
Low Limit [Hz]
. Submersible deep well pumps
can be damaged by running below minimum
speed. A fast ramp time below minimum
pump speed is recommended. This parameter
may be applied as a fast ramp rate from zero
speed to Motor Speed Low Limit.
How to program the adjustab...