29-02 Pipe Fill Speed [Hz]
Range:
Function:
Size related
*
[par. 4-12 - par. 4-14 Hz]
29-03 Pipe Fill Time
Range:
Function:
29-04 Pipe Fill Rate
Range:
Function:
0.001
ProcessCtrlUnit
*
[0.001–
999999.999
ProcessCtrlUnit]
Specifies the filling rate in
units/second using the PI
controller. Filling rate units
are feedback units/second.
This function is used for
filling up vertical pipe
systems but will be active
when the filling time has
expired regardless until
the pipe fill setpoint set in
is reached.
29-05 Filled Setpoint
Range:
Function:
0.000
ProcessCtrlUnit
*
[-999999.999–
999999.999
ProcessCtrlUnit]
Specifies the filled
setpoint at which the
pipe fill function will be
disabled and the PID
controller will take
control. This function can
be used both for
horizontal and vertical
pipe systems.
How to program the adjustab...