6.1.6 Q5 Changes Made
Q5 Changes Made can be used for fault finding.
Select
Changes made
to get information about:
•
the last 10 changes. Use the up/down navigation
keys to scroll between the last 10 changed
parameters.
•
the changes made since default setting.
Select
Loggings
to get information about the display line
readouts. The information is shown as graphs.
Only display parameters selected in par. 0-20 and par. 0-24
can be viewed. It is possible to store up to 120 samples in
the memory for later reference.
Please notice that the parameters listed in the below
tables for Q5 only serve as examples since they will vary
depending on the programming of the particular
adjustable frequency drive.
Q5-1 Last 10 Changes
20-94 PID Integral Time
20-93 PID Proportional Gain
Q5-2 Since Factory Setting
20-93 PID Proportional Gain
20-94 PID Integral Time
Q5-3 Input Assignments
Analog Input 53
Analog Input 54
6.1.7 Q6 Loggings
Q6 Loggings can be used for fault finding.
Please notice that the parameters listed in the table for Q6
below only serve as examples since they will vary
depending on the programming of the particular
adjustable frequency drive.
Q6 Loggings
Reference
Analog Input 53
Motor Current
Frequency
Feedback
Energy Log
Trending Cont Bin
Trending Timed Bin
Trending Comparison
6.1.8 Main Menu Mode
The keypad provides access to the main menu mode.
Select main menu mode by pressing the [Main Menu] key.
Figure 6.2 shows the resulting readout, which appears on
the display of the LCP.
Lines 2 through 5 on the display show a list of parameter
groups which can be chosen by toggling the up and down
buttons.
130BP066.10
1107 RPM
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
3.84 A
1 (1)
Main Menu
Figure 6.9 Display example.
Each parameter has character(s) and number which remain
the same regardless of the programming mode. In main
menu mode, the parameters are further divided into
groups: Macros, Keypad Set-up, Parameter Data Set,
Parameter Data Check, Drive Information, Data Readouts,
Logs & I/O Option Status, and Advanced Parameter Data
Set.
All parameters can be changed in the Main Menu. The
configuration of the unit (
) will
determine other parameters available for programming.
For example, selecting Closed-loop enables additional
parameters related to closed-loop operation. Option cards
added to the unit enable additional parameters associated
with the option device.
6.1.9 Parameter Selection
Main Menu Item
Parameter Groups:
Keypad Set-Up
K-##
Parameter Data Set
F-##, E-##, C-##, P-##, H-##, AN-##, SP-##, O-##, AO-
##, DN-##, PB-##, LN-##, BN-##
Drive Information
ID-##
Data Readouts
DR-##
Logs & I/O Option
Status
LG-##
Advanced Parameter
Data Set
AP-##, FB-##, T-##, CL-##, XC-##, PC-##, LC-##, B-##
Table 6.3 Parameter Groups in Main Menu Items
How to program the adjustab...
VLT AQUA 12-Pulse High Power Instruction Manual
6-6
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark