![Danfoss VLT AQUA Drive FC 200 Instruction Manual Download Page 102](http://html1.mh-extra.com/html/danfoss/vlt-aqua-drive-fc-200/vlt-aqua-drive-fc-200_instruction-manual_3486103102.webp)
6.3.4 Brakes 2-**
Par. No.
#
Parameter description
Default value
4 set-up
Change
during
operation
Conver-
sion index
Type
2-0* DC Brake
2-00
DC Hold/Preheat Current
50 %
All set-ups
TRUE
0
Uint8
2-01
DC Brake Current
50 %
All set-ups
TRUE
0
Uint16
2-02
DC Braking Time
10.0 s
All set-ups
TRUE
-1
Uint16
2-03
DC Brake Cut-in Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
2-04
DC Brake Cut-in Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
2-1* Brake Energy Funct.
2-10
Brake Function
[0] Off
All set-ups
TRUE
-
Uint8
2-11
Brake Resistor (ohm)
ExpressionLimit
All set-ups
TRUE
0
Uint16
2-12
Braking Energy Limit (kW)
ExpressionLimit
All set-ups
TRUE
0
Uint32
2-13
Braking Energy Monitoring
[0] Off
All set-ups
TRUE
-
Uint8
2-15
Brake Check
[0] Off
All set-ups
TRUE
-
Uint8
2-16
AC Brake Max. Current
100.0%
All set-ups
TRUE
-1
Uint32
2-17
Overvoltage Control
[2] Enabled
All set-ups
TRUE
-
Uint8
How to program the adjustab...
VLT AQUA 12-Pulse High Power Instruction Manual
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark
6-39
6
6