Par. No.
#
Parameter description
Default value
4 set-up
Change during
operation
Conver-
sion index
Type
1-7* Start Adjustments
1-71
Start Delay
0.0 s
All set-ups
TRUE
-1
Uint16
1-73
Flying Start
[0] Disabled
All set-ups
FALSE
-
Uint8
1-74
Start Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
1-75
Start Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
1-76
Start Current
0.00 A
All set-ups
TRUE
-2
Uint32
1-8* Stop Adjustments
1-80
Function at Stop
[0] Coast
All set-ups
TRUE
-
Uint8
1-81
Min Speed for Function at
Stop [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
1-82
Min. Speed for Function at
Stop [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
1-86
Trip Speed Low [RPM]
0 RPM
All set-ups
TRUE
67
Uint16
1-87
Trip Speed Low [Hz]
0 Hz
All set-ups
TRUE
-1
Uint16
1-9* Motor Temperature
1-90
Motor Thermal Protection
[4] ETR trip 1
All set-ups
TRUE
-
Uint8
1-91
Motor External Fan
[0] No
All set-ups
TRUE
-
Uint16
1-93
Thermistor Source
[0] None
All set-ups
TRUE
-
Uint8
How to program the adjustab...
VLT AQUA 12-Pulse High Power Instruction Manual
6-38
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark
6