0-20 Display Line 1.1 Small
Option:
Function:
[1639]
Control Card Temp. Temperature of the control card.
[1650]
External Reference
Sum of the external reference as a
percentage, i.e., the sum of
analog/pulse/bus.
[1651]
Pulse Reference
[1652]
Feedback [Unit]
Signal value in units from the
programmed digital input(s).
[1653]
Digi Pot Reference
View the contribution of the
digital potentiometer to the actual
reference Feedback.
[1660]
Digital Input
Displays the status of the digital
inputs. Signal low = 0; Signal high
= 1.
Regarding order, see
16-60 Digital
Input
. Bit 0 is at the extreme right.
[1661]
Terminal 53 Switch
Setting
Setting of input terminal 53.
Current = 0; Voltage = 1.
[1662]
Analog Input 53
Actual value at input 53 either as
a reference or protection value.
[1663]
Terminal 54 Switch
Setting
Setting of input terminal 54.
Current = 0; Voltage = 1.
[1664]
Analog Input 54
Actual value at input 54 either as
reference or protection value.
[1665]
Analog Output 42
[mA]
Actual value at output 42 in mA.
Use
to
select the variable to be
represented by output 42.
[1666]
Digital Output [bin] Binary value of all digital outputs.
[1667]
Freq. Input #29 [Hz] Actual value of the frequency
applied at terminal 29 as a pulse
input.
[1668]
Freq. Input #33 [Hz] Actual value of the frequency
applied at terminal 33 as a pulse
input.
[1669]
Pulse Output #27
[Hz]
Actual value of pulses applied to
terminal 27 in digital output
mode.
[1670]
Pulse Output #29
[Hz]
Actual value of pulses applied to
terminal 29 in digital output
mode.
[1671]
Relay Output [bin]
View the setting of all relays.
[1672]
Counter A
View the present value of Counter
A.
[1673]
Counter B
View the present value of Counter
B.
0-20 Display Line 1.1 Small
Option:
Function:
[1674]
Prec. Stop Counter
[1675]
Analog In X30/11
Actual value of the signal on input
X30/11 (General Purpose I/O Card.
Option)
[1676]
Analog In X30/12
Actual value of the signal on input
X30/12 (General Purpose I/O Card.
Optional)
[1677]
Analog Out X30/8
[mA]
Actual value at output X30/8
(General Purpose I/O Card.
Optional) Use
6-60 Terminal X30/8
Output
to select the variable to be
shown.
[1678]
[1679]
[1680]
Fieldbus CTW 1
Control word (CTW) received from
the bus master.
[1682]
Fieldbus REF 1
Main reference value sent with
control word via the serial
communications network, e.g.,
from the BMS, PLC or other
master controller.
[1684]
Comm. Option
Status
Extended serial communication
option status word.
[1685]
FC Port CTW 1
Control word (CTW) received from
the bus master.
[1686]
FC Port REF 1
Status word (STW) sent to the bus
master.
[1690]
Alarm Word
One or more alarms in a Hex code
(used for serial communications)
[1691]
Alarm word 2
One or more alarms in a Hex code
(used for serial communications)
[1692]
Warning Word
One or more warnings in a Hex
code (used for serial communi-
cations)
[1693]
Warning word 2
One or more warnings in a Hex
code (used for serial communi-
cations)
[1694]
Ext. Status Word
One or more status conditions in
a Hex code (used for serial
communications)
[3401]
PCD 1 Write to
MCO
[3402]
PCD 2 Write to
MCO
[3403]
PCD 3 Write to
MCO
How to program the adjustab...