6.3.9 Comm. and Options 8-**
Par. No.
#
Parameter description
Default value
4 set-up
Change during
operation
Conver-
sion index
Type
8-0* General Settings
8-01
Control Site
null
All set-ups
TRUE
-
Uint8
8-02
Control Source
null
All set-ups
TRUE
-
Uint8
8-03
Control Timeout Time
ExpressionLimit
1 set-up
TRUE
-1
Uint32
8-04
Control Timeout Function
[0] Off
1 set-up
TRUE
-
Uint8
8-05
End-of-Timeout Function
[1] Resume set-up
1 set-up
TRUE
-
Uint8
8-06
Reset Control Timeout
[0] Do not reset
All set-ups
TRUE
-
Uint8
8-07
Diagnosis Trigger
[0] Disable
2 set-ups
TRUE
-
Uint8
8-1* Control Settings
8-10
Control Profile
[0] FC profile
All set-ups
TRUE
-
Uint8
8-13
Configurable Status Word STW
[1] Profile Default
All set-ups
TRUE
-
Uint8
8-14
Configurable Control Word CTW
[1] Profile default
All set-ups
TRUE
-
Uint8
8-3* FC Port Settings
8-30
Protocol
null
1 set-up
TRUE
-
Uint8
8-31
Address
ExpressionLimit
1 set-up
TRUE
0
Uint8
8-32
Baud Rate
null
1 set-up
TRUE
-
Uint8
8-33
Parity / Stop Bits
null
1 set-up
TRUE
-
Uint8
8-35
Minimum Response Delay
ExpressionLimit
1 set-up
TRUE
-3
Uint16
8-36
Max Response Delay
ExpressionLimit
1 set-up
TRUE
-3
Uint16
8-37
Maximum Inter-Char Delay
ExpressionLimit
1 set-up
TRUE
-5
Uint16
8-4* FC MC protocol set
8-40
Message Selection
[1] Standard message 1
2 set-ups
TRUE
-
Uint8
8-5* Digital/Bus
8-50
Coasting Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-52
DC Brake Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-53
Start Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-54
Reversing Select
null
All set-ups
TRUE
-
Uint8
8-55
Set-up Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-56
Preset Reference Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-7* BACnet
8-70
BACnet Device Instance
1 N/A
1 set-up
TRUE
0
Uint32
8-72
MS/TP Max Masters
127 N/A
1 set-up
TRUE
0
Uint8
8-73
MS/TP Max Info Frames
1 N/A
1 set-up
TRUE
0
Uint16
8-74
"I-Am" Service
[0] Send at power-up
1 set-up
TRUE
-
Uint8
8-75
Initialization Password
ExpressionLimit
1 set-up
TRUE
0
VisStr[20]
8-8* FC Port Diagnostics
8-80
Bus Message Count
0 N/A
All set-ups
TRUE
0
Uint32
8-81
Bus Error Count
0 N/A
All set-ups
TRUE
0
Uint32
8-82
Slave Message Rcvd
0 N/A
All set-ups
TRUE
0
Uint32
8-83
Slave Error Count
0 N/A
All set-ups
TRUE
0
Uint32
8-9* Bus Jog/Feedback
8-90
Bus Jog 1 Speed
100 RPM
All set-ups
TRUE
67
Uint16
8-91
Bus Jog 2 Speed
200 RPM
All set-ups
TRUE
67
Uint16
8-94
Bus Feedback 1
0 N/A
1 set-up
TRUE
0
N2
8-95
Bus Feedback 2
0 N/A
1 set-up
TRUE
0
N2
8-96
Bus Feedback 3
0 N/A
1 set-up
TRUE
0
N2
How to program the adjustab...
VLT AQUA 12-Pulse High Power Instruction Manual
6-46
MG.20.Y1.22 - VLT
®
is a registered Danfoss trademark
6
6