Troubleshooting by Remote Controller Display / LED Display
Troubleshooting
185
5.22 “
E7
” Malfunction of Outdoor Unit Fan Motor
Remote
Controller
Display
E7
Applicable
Models
RZQ(S)71~140
Method of
Malfunction
Detection
Abnormality of fan motor system is detected according to the fan speed detected by hall IC
when the fan motor runs.
Malfunction
Decision
Conditions
When the fan runs with speed less than a specified one for 15 seconds or more when the fan
motor running conditions are met
When connector detecting fan speed is disconnected
When malfunction is generated 4 times, the system shuts down.
Supposed
Causes
Malfunction of fan motor
The harness connector between fan motor and PC board is left in disconnected, or faulty
connector
Fan does not run due to foreign matters tangled
Malfunction of the outdoor (inverter) PC board
Blowout of fuse
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...