![background image](http://html1.mh-extra.com/html/daikin/fhq100buv1b-x-2/fhq100buv1b-x-2_service-manual_2459261174.webp)
SiBE28-804
Troubleshooting by Remote Controller Display / LED Display
Troubleshooting
163
Troubleshooting
Check the
connections of X20A
and X26A.
Check indoor unit
fan motor and
motor wiring.
Are
X20A and
X26A
properly
Is
there about
12 VDC?
Unplug X26A
and switch the
power supply on.
Check the voltage
between pins 1
and 3 of X26A.
NO
NO
YES
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connect
X20A and X26A
correctly.
Replace indoor
unit PC board.