Troubleshooting by Remote Controller Display / LED Display
SiBE28-804
170
Troubleshooting
Troubleshooting
Is the
capacity
setting adapter
plugged into X23A of the
indoor unit
PC board?
Is "
AJ
"
displayed on the
remote controller?
Plug a capacitor setting
adapter that matches the
capacity of the unit into X23A.
Switch the power
supply off and
back on again.
Check if the capacity setting
adapter is plugged into X23A of
the indoor PC board.
Replace indoor
unit PC board.
NO
NO
YES
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The malfunction was caused
by a missing capacity resistor.