SiBE28-804
Troubleshooting by Remote Controller Display / LED Display
Troubleshooting
195
5.27 “
J1
” Malfunction of Pressure Sensor
Remote
Controller
Display
J1
Applicable
Models
RZQ71~140C7V1B
RZQS71~140C7V1B
Method of
Malfunction
Detection
The malfunction is detected by the pressure measured with pressure sensor (S1NPH)
Malfunction
Decision
Conditions
When the detect pressure becomes following;
•
Detected pressure
≤
-0.05MPa continues 185 sec.
•
Detected pressure
≥
4.4MPa continues 185 sec.
Supposed
Causes
Faulty pressure sensor
Faulty outdoor unit PC board
Incorrect connection of connector