Troubleshooting
Is the supply
voltage within the range 180 to
220 VAC ?
NO
YES
Ask repair so that the
supply voltage will be
within the normal range.
Turn OFF the power again
(and wait for 10 minutes).
Remove the fan motor
connector.
Is the fan
motor connector correctly
connected to the outdoor PC
board?
NO
YES
Properly connect the
connector.
Is there
any foreign matter around
the fan?
NO
YES
Remove the foreign
matter.
check the resistance
value for the fan motor. (P233)
Is the fan
rotatable easily by hand?
NO
YES
Replace the fan motor.
Check 9
A
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...