General Functionality
SiBE28-804
38
Functional Description
1.4
Simulated Operation Function
RZQ71C7, RZQS71·100C7
When a malfunction on one of the below thermistors occurs, operation will continue while
displaying the applicable alarm on the remote-controller. Fin thermistor malfunction is only
displayed when pressing the "Inspection" button on the remote controller.
· Outside temperature thermistor
· Outdoor heat exchanger thermistor
· Fin thermistor
· Discharge pipe thermistor
· Indoor unit air suction thermistor
· Indoor heat exchanger thermistor (RZQ71C7, RZQS71·100C7)
Note:
Simulated operation will not be conducted in case the below mentioned thermistors are
malfunctioning:
· Suction thermistor
· Indoor heat exchanger thermistor
· Outdoor heat exchanger thermistor
RZQ100~140C7·RZQS125·140C7
In case of a thermistor malfunction, simulated operation is performed in two different ways
as shown below even while the malfunction is detected.
A. Operation continues while the malfunction code is displayed on the remote controller.
Applicable thermistors
· Outside air temperature thermistor
· Heat exchanger distribution pipe thermistor (in cooling operation only)
· Intermediate heat exchanger thermistor (in heating operation only)
· Liquid pipe thermistor
· Indoor suction air thermistor
· Indoor heat exchanger thermistor
B. Operation continues even the malfunction is detected. The remote controller displays
"Inspection/Test Run". Only when the button is pushed, the malfunction code appears.
Applicable thermistors
· Remote controller thermistor
· Radiation fin thermistor
Note:
In case of a thermistor malfunction other than A and B above, a malfunction stop is made and
no simulated operation is carried out.
Applicable thermistors
· Suction pipe thermistor
· Discharge pipe thermistor
· Heat exchanger distribution pipe thermistor (in heating operation only)
· Intermediate heat exchanger thermistor (in cooling operation only)
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...