![background image](http://html1.mh-extra.com/html/daikin/fhq100buv1b-x-2/fhq100buv1b-x-2_service-manual_2459261113.webp)
Field Settings
SiBE28-804
102
Test Operation
b. “Setting mode 2”
In this mode, settings for the following items can be made by using BS buttons.
The figures in the columns under "No." represent the number of times to push the
SET (BS2) button.
Setting of Demand 2 operation
With this setting, compressor operation can be controlled to reduce power consumption.
(60% - 80% demand is available when a demand adapter (optional accessory) is used.)
[Work procedure]
No.
Display of setting items
Display of setting condition
Setting item
LED display
Setting condition
LED display
H1P H2P H3P H4P H5P H6P H7P
H1P H2P H3P H4P H5P H6P H7P
3
Demand 2
operation
8 1 1 1 1 8 8
30% demand
40% demand (factory
setting)
50% demand
8 1 1 1 8 1 1
8 1 1 1 1 8 1
8 1 1 1 1 1 8
28
Refrigerant
recovery mode
8 1 8 8 8 1 1
OFF (factory setting)
ON
8 1 1 1 1 1 8
8 1 1 1 1 8 1
Setting item
Setting condition
Description
Demand 2 operation
30% demand
Operates with 30% of rated
power consumption.
40% demand (factory setting)
Operates with 40% of rated
power consumption.
50% demand
Operates with 50% of rated
power consumption.
1
: OFF
9
: BLINK
8
: ON
Operating procedure
H1P H2P H3P H4P H5P H6P H7P
Push and hold the MODE (BS1) button of "Setting mode 1" for 5 seconds
or more and set to "Setting mode 2."
8 1 1 1 1 1 1
Push the SET (BS2) button three times to set the LED display as shown
in the table on the right.
8 1 1 1 1 8 8
Push the RETURN (BS3) button once. (Present settings are displayed.)
8 1 1 1 1 9 1
Push the SET (BS2) button to set the LED
display as shown in the table on the right.
30% of rated power consumption
8 1 1 1 9 1 1
40% of rated power consumption
8 1 1 1 1 9 1
50% of rated power consumption
8 1 1 1 1 1 9
Push the RETURN (BS3) button once to make a
decision.
30% of rated power consumption
8 1 1 1 8 1 1
40% of rated power consumption
8 1 1 1 1 8 1
50% of rated power consumption
8 1 1 1 1 1 8
Push the RETURN (BS3) button once again for execution. (The LED
display is in the initial status of "Setting mode 2".)
8 1 1 1 1 1 1
Push the MODE (BS1) button once to return to Setting mode 1 (normal
operation).
1 1 1 1 1 1 1
Push and hold the MODE (BS1) button
for 5 seconds and set to “Setting mode
2”.
Push the SET (BS2) button and set the
LED display to a setting item shown in
the table on the right.
↓
Push the RETURN (BS3) button and
decide the item. (The present setting
condition is blinked.)
<Selection of setting items>
<Selection of setting conditions>
Push the SET (BS2) button and set to
the setting condition you want.
↓
Push the RETURN (BS3) button and
decide the condition.
Push the RETURN (BS3) button and
set to the initial status of “Setting mode
2”.
∗
If you become unsure of how to proceed,
push the MODE (BS1) button and return
to setting mode 1.
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...