General Functionality
SiBE28-804
50
Functional Description
1.14 PMV Control
Outline
When the automatic mode is selected on the remote-controller, the unit will automatically
activate the PMV control.
The PMV index is a calculated average comfort level.
Refer to ISO 7730 for details.
Function
An optimized indoor temperature will be calculated using the following inputs:
Outdoor air temperature
Indoor air temperature
Remote controller set temperature
In practice, the set point will be moved with 1 or 2 degrees whenever the conditions change.
This will result in a combination of power saving and increased comfort level.
PMV control can be disabled by changing the field settings:
From: 11(21)-4-01 to: 11(21)-4-02