Frequency Regulating Functions
SiBE28-804
66
Functional Description
Frequency steps
The operating frequency for the sky-air RZQ(S) inverter units will be a value chosen from a list
with fixed frequency settings that is programmed in the unit's memory:
: Maximum frequency in cooling
Maximum frequency in RZQ/RZQS71
Step No.
Compressor operation frequency
RZQ71C7,
RZQS71·100C7
RZQ100~140C7
RZQS125·140C7
1
48 Hz
32 Hz
2
52.5 Hz
36 Hz
3
57 Hz
41 Hz
4
61.5 Hz
44 Hz
5
66 Hz
48 Hz
6
72 Hz
52 Hz
7
78 Hz
57 Hz
8
85.5 Hz
62 Hz
9
93 Hz
67 Hz
10
100.5 Hz
72 Hz
11
109.5 Hz
78 Hz
12
118.5 Hz
84 Hz
13
127.5 Hz
90 Hz
14
136.5 Hz
94 Hz
15
145.5 Hz
98 Hz
16
154.5 Hz
102 Hz
17
163.5 Hz
107 Hz
18
174 Hz
112 Hz
19
183 Hz
117 Hz
20
192 Hz
123 Hz
21
201 Hz
131 Hz
22
211.5 Hz
139 Hz
23
222 Hz
147 Hz
24
232.5 Hz
155 Hz
25
243 Hz
164 Hz
26
253.5 Hz
—
27
265.5 Hz
—
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...