SiBE28-804
Troubleshooting by Remote Controller Display / LED Display
Troubleshooting
215
Troubleshooting
Is
the power
supply voltage between
220~240 VAC
±10%?
Check
LED on outdoor
unit PC board. (Is the
voltage insufficient?)
NO
When the compressor is
running, measure the voltage
b and - of
electrolytic capacitor (C+, C-).
Is the wiring correct?
Is the
measured voltage
220 VDC or more?
NO
YES
YES
YES
YES
NO
NO
Field factors
Correct the wiring.
Monitor the voltage
(Instantaneous voltage drop)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Other factors
Replace the outdoor PC board
(A2P).