![background image](http://html1.mh-extra.com/html/daikin/fhq100buv1b-x-2/fhq100buv1b-x-2_service-manual_2459261125.webp)
Field Settings
SiBE28-804
114
Test Operation
Graph 3
Target evaporating temperature control when "low humidity appli freeze up operation
prevention" is selected. Field setting 16(26)-2-04:
Note:
Change
thermostat
control
In order to increase continuous operation of the unit in low latent heat applications and avoid the
rise of temperature after thermostat OFF, the thermostat control will be changed when using
field settings 16(26)-2-03 & 16(26)-2-04.
Thermostat ON
∆
Trs
≥
0.5 °C (No change from standard setting)
Thermostat OFF
∆
Trs
≤
-2.0 °C for 5 minutes continuously.
∆
Trs
≤
4.5 °C
Remote controller setting temp.
Te target limitted
≤
20˚C
(to protect the comp.)
Te (see note) target acceptable area
Indoor temp.
>
setting
→
Te target down
Indoor temp.
<
setting
→
Te target up
Te target limitted
≥
2˚C
(not to freeze)
Freeze protection
(40min. integrated coil temp.
≤
-1˚C)
Te target acceptable area
Te target
(˚C)
Indoor Temp
(˚C DB)
Te by LP sensor
RZQ71~140C7V1B, RZQS71~140C7V1B
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...