Test Run and Operation Data
SiBE28-804
116
Test Operation
3. Test Run and Operation Data
3.1
General Operation Data
Guide Lines for
Optimal
Operation
Condition
The operation value guide lines when operating under standard conditions
(at Rated
frequency)
by pushing the test run button on the remote controller are as given in the table
below.
Indoor Unit Fan:
“H” Operation Compressor: Rated Frequency
High
Pressure
(Mpa)
Low
Pressure
(Mpa)
Discharge
Pipe
Temperature
(°C)
Suction
Temperature
(°C)
Indoor Unit
Side:
Differential
Between
Suction
Temperature
and
Discharge
Temperature
(°C)
Outdoor Unit
Side:
Differential
Between
Suction
Temperature
and
Discharge
Temperature
(°C)
Cooling
26 bar ~
34 bar
6 bar ~
10 bar
60~100
–2~10
8~18
7~12
Heating
25 bar ~
32.6 bar
5.3 bar ~
7.5 bar
60~100
–6~2
14~30
2~6
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...