Troubleshooting by Remote Controller Display / LED Display
SiBE28-804
184
Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
NO
NO
YES
Is the
UVWN wiring
normal?
NO
YES
Is the
stop valve
open?
YES
NO
NO
Is high
pressure higher
than 2.6 MPa
at starting?
YES
NO
Check
and see
whether compressor is
short-circuited or
ground.
YES
Are
inverter output
voltages the same for
3 phases?
Does low or
high pressure vary
even instantaneously
when restarting
compressor?
Check the installation
conditions.
Open the stop valve.
Connect correctly.
Remedy the cause.
Replace the compressor.
Replace the inverter PC board.
Replace the compressor.