Precautions for New Refrigerant (R-410A)
SiBE28-804
294
Precautions for New Refrigerant (R-410A)
4. Leak tester
Specifications
2
Hydrogen detecting type, etc.
2
Applicable refrigerants
R-410A, R-407C, R-404A, R-507A, R-134a, etc.
Differences
2
Previous testers detected chlorine. Since HFCs do not contain chlorine, new tester detects
hydrogen.
5. Refrigerant oil (Air compal)
Specifications
2
Contains synthetic oil, therefore it can be used for piping work of every refrigerant cycle.
2
Offers high rust resistance and stability over long period of time.
Differences
2
Can be used for R-410A and R-22 units.
6. Gauge manifold for R-410A
Specifications
2
High pressure gauge
- 0.1 to 5.3 MPa (-76 cmHg to 53 kg/cm
2
)
2
Low pressure gauge
- 0.1 to 3.8 MPa (-76 cmHg to 38 kg/cm
2
)
2
1/4"
→
5/16" (2min
→
2.5min)
2
No oil is used in pressure test of gauges.
→
For prevention of contamination
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...