Troubleshooting by Remote Controller Display / LED Display
SiBE28-804
174
Troubleshooting
Troubleshooting
Check the connector
connection.
Replace outdoor
unit PC board.
Is it connected
properly?
Is it normal?
Is the
contact OK?
Check the thermistor
resistance.
Check the contact between
thermistor and PC board.
NO
NO
NO
YES
YES
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Correct the
connection.
Replace the
thermistor.
Correct contact.
C4
: Indoor liquid pipe thermistor (R2T).
C9
: Air suction thermistor (R1T).