![background image](http://html1.mh-extra.com/html/daikin/fhq100buv1b-x-2/fhq100buv1b-x-2_service-manual_2459261210.webp)
SiBE28-804
Troubleshooting by Remote Controller Display / LED Display
Troubleshooting
199
5.29 “
L4
” Radiation Fin Temperature Increased
Remote
Controller
Display
L4
Applicable
Models
RZQ(S)71~140
Method of
Malfunction
Detection
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Decision
Conditions
When the temperature of the inverter radiation fin increases abnormally due to faulty heat
dissipation.
Supposed
Causes
Activation of fin thermal switch
Faulty fin thermistor
High outside air temperature
Insufficient cooling of inverter radiation fin
Blocked suction opening
Dirty radiation fin
Faulty outdoor inverter PC board