SiBE28-804
Indoor Unit Functional Concept
Functional Description
57
2.5
Draft Avoidance Control 2
Purpose
The purpose of the draft avoidance control 2 is to avoid draft when the flap is moving.
Starting
conditions
The draft avoidance control 2 is activated when:
Hot start is finished, or
Cold air prevention control is finished.
Time chart
If the fan speed is set to "H", the fan turns at low speed for a certain amount of time.
Used input
Draft avoidance control 2 uses the following inputs:
Fan
Flap
Hot start finished
Setting
OFF/LL
L
H
Po0
T
T = 24 s
FCQ: T = 5s
Input
Connection on
indoor PCB
Connection on
outdoor PCB
Limit switch for flaps
33S
—
No. of fan turns
X26A
—