SiBE28-804
Frequency Regulating Functions
Functional Description
73
4.9
Protection Control by Overall Current
Monitors the overall current and restricts the upper limit compressor operating frequency to
prevent circuit breakers from exceeding the rated capacity.
Upper limit current (A)
Takes the following values depending on the outside temperature.
Also varies depending on model.
RZQ71C7,
RZQS71
RZQS100C7V1B
RZQ100~140C7,
RZQS125·140C7V1B
A
16.5 A
18.0 A
24.0 A
B
16.5 A
18.0 A
24.0 A
C
13.4 A
19.0 A
23.0 A
D
10.0 A
13.3 A
16.0 A
E
10 (sec.)
10 (sec.)
10 (sec.)
Normal operation
Outdoor unit current
≤
upper limit
current value
Upper limit compressor operating
frequency = Maximum frequency
Outdoor unit current
≤
upper
limit current value
Outdoor unit current
>upper limit current value
Upper limit compressor operating frequency
–1 step/E sec.
Upper limit compressor operating frequency
+1 step/2 min
Outdoor unit current>upper
limit current value
&
Current A
Current C
Current B
Current D
25
Ta
28
43
50
Overall current
(A)
Outdoor air temp. (˚C)
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...