SiBE28-804
Test Run and Operation Data
Test Operation
117
Standard
Conditions
During or after maintenance, when the power supply is turned back on, operation restarts
automatically by the “auto restart function.” Please exercise the proper caution.
When perfoming maintenance, you should at least perform the following inspections:
Indoor Unit Conditions
Outdoor Unit Conditions
Cooling Operation
27°C DB/19°C WB
35°C DB
Heating Operation
20°C DB
7°C DB/6°C WB
Indoor unit
Outdoor unit
Earth
Drain piping
Refrigerant piping
Transmission wiring between
indoor and outdoor units
To dedicated
breaker
Is the air filter dirty?
What about voltage and current?
What about switch capacity?
What about cable thickness?
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...