![background image](http://html1.mh-extra.com/html/daikin/fhq100buv1b-x-2/fhq100buv1b-x-2_service-manual_2459261103.webp)
Field Settings
SiBE28-804
92
Test Operation
2.3
Overview of the Field Settings on the Indoor Units
Field settings
The table below contains the possible field settings of all indoor units.
Mode
No.
First
code No.
Description of the setting
Second code No.
01
02
03
04
10 (20)
0
Filter counter
Light
contamination
heavy
contamination
—
—
1
Filter type
Long
Super long
External
Oil mist
2
Remote thermistor of the
remote controller
TH1 = rem.
controller
TH1 = air
return
—
—
3
Filter display
Filter indic.
No filter indic.
—
—
11 (21)
0
Number indoor to 1 outdoor
Pair
Twin
Triple
Double twin
1
Unified or indiv. set twin
Group setting
Indiv. setting
—
—
2
Fan OFF at thermostat OFF
LL-speed
OFF
—
—
7
Airflow automatic adjustment
OFF
Completion of
Airflow
Adjustment
Start of Airflow
Adjustment
—
12 (22)
0
KRP1B51/52/53 X1/X2 output
Thermostat
ON
Option
Operation
Malfunction
1
EKRORO
Forced OFF
ON/OFF
operation
—
—
3
Fan speed heating thermostat
OFF
LL-speed
Set speed
—
—
5
Automatic restart
Disabled
Enabled
—
—
13 (23)
0
Ceiling height setting
Normal
High
Extra high
—
≤
2.7 m
>2.7
≤
3.0 m
>3.0
≤
3.5 m
—
1
Selection of air flow direction
(setting for when a blocking
pad kit has been inst alled).
4-way flow
3-way flow
2-way flow
—
3
Horizontal discharge grill
Enabled
Disabled
—
—
4
Air flow direction adjust range
setting
Draft
prevention
Standard
Ceil soil
prevention
—
5
Field fan speed changeover air
outlet (domestic only)
Standard
Option 1
Option 2
—
6
External static pressure
14 (24)
0
Additional timer to guard timer
0 s
5 s
10 s
15 s
1b
(Only in
case of
BRC1D52)
0
Permission level setting
Level 2
Level 3
—
—
1
Leave home function
Not
permitted
Permitted
—
—
2
Thermostat sensor in remote
controller (for limit operation
and leave home function only)
Use
Not use
—
—
01
02
03
04
05
06
07
08
09
10
11
12
13
14
50pa
60pa
90pa
80pa
90pa
100pa 110pa 120pa 130pa 140pa 150pa 160pa 180pa 200pa
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...