SiBE28-804
Field Settings
Test Operation
105
d. “List of contents of retry and malfunction”
Take the following steps to check contents of retry and malfunction.
8
: ON
1
: OFF
9
: BLINK
Malfunction
code
Contents of retry or malfunction
1
2
3
HAP H1P H2P H3P H4P H5P H6P H7P HAP H1P H2P H3P H4P H5P H6P H7P HAP H1P H2P H3P H4P H5P H6P H7P
C4
Indoor heat exchanger thermistor
9 9 8 7 7 7 9 7 9 9 8 7 7 9 7 7 9 9 8 8 7 7 7 7
E1
Faulty outdoor PC board
9 9 7 8 7 7 9 9 9 9 8 7 7 7 7 9 9 9 8 8 7 7 7 7
E3
Abnormal high pressure
9 9 8 7 7 7 9 9 9 9 8 8 7 7 7 7
E4
Abnormal low pressure
9 9 8 7 7 9 7 7 9 9 8 8 7 7 7 7
E5
Compressor motor lock
9 9 8 7 7 9 7 9 9 9 8 8 7 7 7 7
E7
Abnormal outdoor
fan motor
DC motor 1 lock
9 9 8 7 7 9 9 9 9 9 8 8 7 7 7 9
DC motor 2 lock
9 9 8 8 7 7 9 7
Abnormal inverter transmission
9 9 8 8 7 7 9 9
E9
Abnormal electronic
expansion valve
Disconnected electronic expansion valve connector
9 9 8 7 9 7 7 9 9 9 8 8 7 7 7 9
Malfunction due to wet conditions
9 9 8 8 7 7 9 7
F3
Abnormal discharge
pipe temperature
Abnormal discharge pipe temperature
9 9 7 8 7 9 7 9 9 9 8 7 7 7 9 9 9 9 8 8 7 7 7 9
Disconnected discharge pipe thermistor
9 9 8 8 7 7 9 7
H3
Abnormal high pressure switch
9 9 7 8 7 9 7 7 9 9 8 7 7 7 9 9 9 9 8 8 7 7 7 7
H9
Abnormal outdoor air thermistor
9 9 8 7 9 7 7 9 9 9 8 8 7 7 7 7
J1
Abnormal pressure sensor
9 9 7 8 7 9 9 7 9 9 8 7 7 7 7 9 9 9 8 8 7 7 7 7
J3
Abnormal discharge pipe thermistor
9 9 8 7 7 7 9 9 9 9 8 8 7 7 7 7
J5
Abnormal suction pipe thermistor
9 9 8 7 7 9 7 9 9 9 8 8 7 7 7 7
J6
Abnormal heat exchanger distributor pipe thermistor
9 9 8 7 7 9 9 7 9 9 8 8 7 7 7 7
J7
Abnormal intermediate heat exchanger thermistor
9 9 8 7 7 9 9 9 9 9 8 8 7 7 7 7
J8
Abnormal liquid pipe thermistor
9 9 8 7 9 7 7 7 9 9 8 8 7 7 7 7
L1
PC board failure
9 9 7 8 7 9 9 9 9 9 8 7 7 7 7 9 9 9 8 8 7 7 7 7
L4
Elevated radiation fin temperature
9 9 8 7 7 9 7 7 9 9 8 8 7 7 7 7
L5
Compressor instantaneous overcurrent
9 9 8 7 7 9 7 9 9 9 8 8 7 7 7 7
L8
Compressor overload
9 9 8 7 9 7 7 7 9 9 8 8 7 7 7 7
L9
Compressor lock
9 9 8 7 9 7 7 9 9 9 8 8 7 7 7 7
LC
Abnormal transmission (between the control and the inverter)
9 9 8 7 9 9 7 7 9 9 8 8 7 7 7 7
P1
Unbalanced power supply voltage
9 9 7 8 9 7 7 7 9 9 8 7 7 7 7 9 9 9 8 8 7 7 7 7
P4
Abnormal radiation fin thermistor
9 9 8 7 7 9 7 7 9 9 8 8 7 7 7 7
PJ
Faulty capacity setting
9 9 8 7 9 9 7 9 9 9 8 8 7 7 7 7
U0
Abnormal gas
shortage
Gas shortage warning
9 9 7 8 9 7 7 9 9 9 8 7 7 7 7 7 9 9 8 8 7 7 7 9
Abnormal gas shortage
9 9 8 8 7 7 9 7
U2
Abnormal power
supply voltage
Inverter undervoltage and overvoltage
9 9 8 7 7 7 9 7 9 9 8 8 7 7 7 9
SP-PAM overvoltage
9 9 8 8 7 7 9 7
U4
Abnormal transmission (between indoor and outdoor units)
9 9 8 7 7 9 7 7 9 9 8 8 7 7 7 7
UA
Faulty field setting switch
9 9 8 7 9 7 9 7 9 9 8 8 7 7 7 7
UF
Improper piping and improper communication wiring
9 9 9 9 9 9 8 8 7 7 7 7
To enter "Monitor mode," push the MODE (BS1)
button when in "Setting mode 1."
Push the SET (BS2) button to set the LED
display to retry or malfunction item.
When the RETURN (BS3) button is pushed, the
LED display for RETURN 1 turns ON.
<Selection of retry or malfunction item>
When SET (BS2) button is pushed, the LED
display for RETURN 2 turns ON.
<Display of RETURN 2>
When SET (BS2) button is pushed, the LED
display for RETURN 3 turns ON.
Push the RETURN (BS3) button to return the
system to the initial state of "Monitor mode."
∗
Pushing the MODE (BS1) button will bring the
system to the "Setting mode 1."
<Display of RETURN 3>
<Display of RETURN 1>
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...