Piping Diagrams
SiBE28-804
256
Appendix
3.7.6 Refrigerant Pipe Size
Pipe size down and pipe size up is available for main piping (L1) only.
Not using the standard pipe size may result in capacity decrease. It is up to the installer to
judge on this phenomenon carefully in function of the complete installation.
Refrigerant pipe size
Gas pipe
Model
Size-down
Standard size
Size-up
RZQ(S)71
φ
12.7
φ
15.9
––
RZQ(S)100~140
––
φ
19.1
Liquid pipe
Model
Size-down
Standard size
Size-up
RZQ(S)71~140
φ
6.4
φ
9.5
φ
12.7