Troubleshooting by Remote Controller Display / LED Display
Troubleshooting
233
Outdoor Unit: Fan Motor Signal Line
For RZQ(S)71~140 models
(1) Turn the power supply off.
(2) With the fan motor connector disconnected, measure the resistance between each pin, then
make sure that the resistance is more than the value mentioned in the following table.
Check No.9
Measurement point
Judgment
1 - 4
1M
Ω
or more
2 - 4
100k
Ω
or more
3 - 4
100
Ω
or more
4 - 7
100k
Ω
or more
1 White
2 Orange
3 Brown
4 Blue
5
6
7 Red
GND
(S2675)