SiBE28-804
Field Settings
Test Operation
101
Setting by BS buttons
With "Setting mode 1," "Setting mode 2" and "Monitor mode," various settings and data can be
checked.
Setting mode 1
The initial status (normal operation) is "Setting mode 1." This mode indicates operating status -
"TEST (test operation)," "HWL (malfunction)," "L.N.O.P (low noise operation)" or "DEMAND
(demand operation)."
Setting mode 2
Each operating status can be modified.
Monitor mode
This mode indicates "oil return operation," "outdoor unit class," "contents of retry," "contents of
malfunction," "causes of stepping-down operation," etc.
a. “Setting mode 1”
Using this mode, the following conditions can be checked:
•
Current operating condition (normal/test operation/line inspection and normal/malfunction)
•
Low noise operating condition (normal/low noise level setting)
•
Demand operating condition (normal/demand level 1, 2 and 3)
These conditions above can be checked by performing the following steps:
Setting mode 1
Monitor mode
H1P
Push the BS1(MODE button)
one time.
Blinking
MODE
MODE
Off
H1P
Setting mode 2
MODE
On
H1P
Push and hold the BS1
(MODE button) for 5 seconds.
Push the BS1(MODE button) one time.
(Normal)
(V2761)
Using the MODE button, the modes can be changed as follows.
During "Setting mode 1," the lamp is always OFF.
Test operation display
7
In normal operation
8
In test operation
9
In line inspection operation
Malfunction display
7
Normal
8
Malfunction
Low noise operation display
77
Normal operation
87
Low noise level setting
Demand level display
77
Normal operation
78
Demand level 1
87
Demand level 2
88
Demand level 3
8
: ON
9
: OFF
7
: BLINK
MODE
H1P H2P H3P H4P H5P H6P H7P
TEST HWL
L.N.O.P
DEMAND
7
7
7
7
7
7
7
The system is normally set to "Setting
mode 1".
Should the system be set to any
mode other than that, push the
MODE (BS1) button to set the
system to "Setting mode 1".
Check the system for each condition
through LED displays. (Refer to
information in table on the right.)
Procedure for checking check items
Summary of Contents for FHQ100BUV1B x 2
Page 13: ...SiBE28 804 2 ...
Page 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Page 29: ...Specifications SiBE28 804 18 Specifications ...
Page 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Page 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Page 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Page 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Page 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Page 277: ...PCB Layout SiBE28 804 266 Appendix ...
Page 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Page 311: ...SiBE28 804 iv Index ...