![background image](http://html1.mh-extra.com/html/daikin/fhq100buv1b-x-2/fhq100buv1b-x-2_service-manual_2459261202.webp)
SiBE28-804
Troubleshooting by Remote Controller Display / LED Display
Troubleshooting
191
5.24 “
F3
” Malfunctioning in Discharge Pipe Temperature
Remote
Controller
Display
F3
Applicable
Models
RZQ(S)71~140
Method of
Malfunction
Detection
Abnormality is detected according to the temperature detected by the discharge pipe
temperature sensor.
Malfunction
Decision
Conditions
When the discharge pipe temperature rises to an abnormally high level
When the discharge pipe temperature rises suddenly
Supposed
Causes
Faulty discharge pipe thermistor
Faulty connection of discharge pipe thermistor
Insufficient refrigerant amount
Faulty compressor
Disconnection of discharge pipe thermistor