Troubleshooting by Remote Controller Display / LED Display
SiBE28-804
216
Troubleshooting
5.39 “
U4
”, “
UF
” Malfunction of Transmission between Indoor
and Outdoor Unit
Remote
Controller
Display
U4
or
UF
Applicable
Models
RZQ(S)71~140
Error generation
The error is generated when the microprocessor detects that the transmission between the
indoor and the outdoor unit is not normal over a certain amount of time.
Supposed
Causes
The possible causes are:
Wiring indoor-outdoor transmission wire is incorrect
Malfunctioning indoor unit PC board
Malfunctioning outdoor unit PC board
burning out fuse
Faulty fan motor
Outside cause (noise...).